Otahuhu B Power Station condenser in-leakage analysis and condensate monitoring system : a thesis presented in partial fulfilment of the requirements for the degree of Master of Engineering in Electronics Engineering at Massey University, Wellington, New Zealand

dc.contributor.authorZhang, Heng
dc.date.accessioned2009-07-22T23:04:40Z
dc.date.availableNO_RESTRICTIONen_US
dc.date.available2009-07-22T23:04:40Z
dc.date.issued2008
dc.description.abstractConsiderable ongoing risk of condenser in-leakage exists at Otahuhu B (OTB) Power Station. The condenser cooling water used at OTB station is corrosive brackish water with exceedingly high sodium and chloride concentrations. Significant signs of corrosion inside the condenser have been found recently. In the event of condenser in-leakage, the salt contaminants in the cooling water will directly enter the Heat Recovery Steam Generator (HRSG) with the potential for significant and costly damage resulting in a long plant outage. A dynamic mathematical model was developed in the thesis to analyse the consequences of condenser in-leakage at OTB station. The analysis results show that the tolerance of the condenser to any leakage of cooling water is almost zero. Because the existing condensate monitoring system is not designed to detect contamination in this time frame, a new fast response system is required to detect condenser in-leakage immediately. A new dedicated fast response condensate monitoring system has been engineered and installed at OTB station as a part of the project scope. The new system dramatically reduces the response time to condenser in-leakage events. Critical instruments utilise multiple redundancy schemes to enhance the availability and reliability of the system. In addition, action level voting, timing, and alarming has been automated to assist operators in making correct decisions. The new condensate monitoring system is presently fully functional. The project has successfully achieved the objective of controlling the risk of condenser in-leakage events and minimising damage and negative effects on the plant.en_US
dc.identifier.urihttp://hdl.handle.net/10179/950
dc.language.isoenen_US
dc.publisherMassey Universityen_US
dc.rightsThe Authoren_US
dc.subjectCorrosionen_US
dc.subjectCondensate monitoring systemen_US
dc.subjectCooling wateren_US
dc.subject.otherFields of Research::290000 Engineering and Technology::290900 Electrical and Electronic Engineering::290903 Other electronic engineeringen_US
dc.titleOtahuhu B Power Station condenser in-leakage analysis and condensate monitoring system : a thesis presented in partial fulfilment of the requirements for the degree of Master of Engineering in Electronics Engineering at Massey University, Wellington, New Zealanden_US
dc.typeThesisen_US
massey.contributor.authorZhang, Heng
thesis.degree.disciplineElectronics Engineeringen_US
thesis.degree.grantorMassey Universityen_US
thesis.degree.levelMastersen_US
thesis.degree.nameMaster of Engineering (M.E.)en_US
Files
Original bundle
Now showing 1 - 2 of 2
Loading...
Thumbnail Image
Name:
02whole.pdf
Size:
12 MB
Format:
Adobe Portable Document Format
Description:
Loading...
Thumbnail Image
Name:
01front.pdf
Size:
152.93 KB
Format:
Adobe Portable Document Format
Description:
License bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
license.txt
Size:
895 B
Format:
Item-specific license agreed upon to submission
Description: